A food truck fire suppression system sits in the hood and goes off on its own. Fusible links over the cooking line separate when the heat passes their rating, which releases a cartridge of nitrogen or carbon dioxide. That gas pushes wet chemical agent through nozzles onto the appliances, into the hood plenum and up the duct.

At the same moment, a valve shuts off the gas to the cooking equipment, and electric appliances are cut off too. The agent mixes with hot grease into a foam that seals in the vapors and helps keep the fire from flaring back up. A manual pull station lets the cook set it off without waiting for the links. The [Ansul R-102 manual](https://www.captiveaire.com/manuals/fire-systems/r-102-manual.pdf) shows the full sequence.

The system needs an inspection at least every 6 months and after major hood cleaning. A portable Class K extinguisher is still required, as do food trucks need a fire suppression system and the Type I hood entry explain.